Diagnostic Condition Description
LOW H
2
O FLOW Low or restricted water flow through the heat pump.
The external bypass valve is in the wrong position, or the water
flow switch has malfunctioned. The water flow switch opens creating
a fault and the heat pump shuts off.
The LCD screen will display LOW H
2
O FLOW on the top line until
the switch closes. The ON LED will flash once every 2 seconds.
LOW COIL TEMPERATURE When the evaporator coil temperature is below 30°F, the heat pump
cannot operate effectively.
The coil thermistor reads the temperature and the control goes into
defrost if the defrost mode is not set to OFF in setup mode.
The LCD display will display LOW COIL TEMP on the top line for
the duration of the low coil temperature condition when the defrost
mode is set to OFF. When set to either Air Defrost or Reversing
Valve Defrost, the LCD display will show * Defrost Mode * for the
duration of the low coil temperature condition.
LOW REFRIGERANT PRESSURE When the ambient temperature is low, the suction pressure can
drop significantly.
This fault will cause the low pressure switch to open and the control
will shut off the compressor.
The LCD display will display LOW REFRIGERANT on the top line
and PRESSURE on the bottom line for the duration of the fault
condition. The ON LED will flash twice every 2 seconds.
HIGH REFRIGERANT PRESSURE When the head pressure builds too high, the high pressure switch
will open causing the heat pump to shut off immediately.
The control will sense this fault condition and shut off the
compressor until the switch re-closes.
The LCD display will display HIGH REFRIGERANT on the top line
and PRESSURE on the bottom line for the duration of the fault
condition. The ON LED will flash 3 times every 2 seconds.
HIGH WATER TEMPERATURE When the POOL or SPA water temperature heats to the maximum
allowed temperature or above, there could be safety risks for
anyone in the water.
The water thermostat will read this temperature and the control will
shut off the heat pump unless it is in CHILLER mode.
The LCD display will display HIGH H
2
0 on the top line and
TEMPERATURE on the bottom line for the duration of the fault
condition. This feature also remains active when the control calls
for heat through a remote thermostat. This is to insure that water
temperature does not go to an abnormally high level due to a
possible malfunction of the remote sensor.
8.2 Diagnostics
In the event a pressure switch opens or another
fault condition occurs, the LCD screen will display
the fault until the problem has been resolved. Please
refer to the following table for the list of diagnostic
conditions.