Note: Bolts and bolt anchors are not included with
the heat pump. The installer must provide 1/4”
x 1-3/8” stainless steel anchor bolts and the
appropriate size concrete anchor to mount the
clamp to the equipment pad.
3. Place the clamps at the base of the heat pump in
the locations indicated in Figure 2.
4. Fit the hook of each clamp over the lip on the
base panel of the heat pump. The hook should
t between the lip of the base panel and the
evaporator coil guard (see Figure 3).
5. Mark the position of the hole in each clamp on the
equipment pad.
6. Drill a hole in the cement using a masonry drill
bit, with a diameter as determined by the concrete
anchor, at each of the marks on the equipment pad.
The hole should be approximately 1-1/2” deep.
7. Insert a bolt anchor into each of the holes. Be sure
the anchors are set completely into the holes
8. Position the anchor clamps so that the holes in the
clamps are over the bolt anchors. Be sure that the
clamp hooks are over the lip of the heat pump base
(see Figure 3)
9. Insert an anchor bolt through each clamp into the
anchor and tighten to secure the clamp and heat
pump to the equipment pad.
Section 3. Water Connections
3.1 Plumbing Layout
Figure 4 illustrates the standard plumbing layout
with a single heat pump unit. Following the diagram
from right to left, the plumbing sequence is as follows:
Pool > Pool Pump > Filter > Heat Pump > Check
Valve > Chemical Loop > Chlorinator > Pool
NOTE For normal installations, do not install a shutoff
valve or any kind of variable restriction in the
water piping between the heat pump outlet and
the pool/spa.
The heat pump must be protected from back-
siphoning of water. If there is any chance of back-
siphoning, provide a check valve between the pool
and the filter pump inlet. Arrangement of pool system
components other than as illustrated in the preceding
Figure 3. Anchor Clamp Installation









Figure 4. Standard Plumbing Layout